Yaskawa VS-616G5 DeviceNet Communication Interface Card SI-M2 User Manual
Page 9

VS-616G5 Option Instruction Manual: DeviceNet™ Communication Interface Card SI-M2
Page 9
Supported Objects (cont.)
Note: The Assembly object is included as a “stub” only to provide data for the DeviceNet Conformance Test.
Connection Object (Class 05h)
Services supported:
Get Attribute Single (0Eh)
Set Attribute Single (10h)
Number of instances = 2
Instance 2: Attributes Supported
Attribute
Get
Set
Description
Size
Default Value
1
X
—
Number of members in list
Word
4
2
X
—
Member List
Struct
—
3
X
X
Data
Array
—
Class level: Attributes Supported (Instance 0)
Attribute
Get
Set
Description
Size
Default Value
1
X
—
Object Software Revision
Word
1
Instance 1: Attributes Supported
Attribute
Get
Set
Description
Size
Default Value
1
X
—
State
Byte
3
2
X
—
Instance type
Byte
0
3
X
—
Transport class trigger
Byte
83h
4
X
—
Produced connection ID
Word
—
5
X
—
Consumed connection ID
Word
—
6
X
—
Initial comm characteristics
Byte
21h
7
X
—
Produced connection size
Byte
—
8
X
—
Consumed connection size
Byte
—
9
X
X
Expected packet rate
Word
09C4h
12
X
—
Watchdog time-out action
Byte
1
13
X
—
Produced connection path length
Word
0
14
X
—
Produced connection path
Array
—
15
X
—
Consumed connection path length
Word
0
16
X
—
Consumed connection path
Array
—