Product Transition Guide
Appendix 2- Parameter Differences

____________________________
PL.F7.02.TransitionGuide 6/5/06
Page 36 of 40
Yaskawa Electric America, Inc

GPD515/G5 Parameters

F7 Parameters

Parameter

No.

Name

(DigitalOperator

Display)

Setting or Selection

Parameter

No.

Name

(Digital Operator Display)

Remarks on

Setting or Selection

L6-01

Overtorque
Detection Selection 1

0: Disabled
1: @SpdAgree - Alm
2: At RUN - Alarm
3: @SpdAgree - Flt
4:At RUN - Fault

L6-01

Torque Detection
Selection 1

Additional selections:
5: UL3 at SpeedAgree -
Alarm Undertorque Detec tion
is only active during Speed
Agree and operation continues
after detection.
6: UL3 at RUN - Alarm
Undertorque Detection is
always active and operation
continues after detection.
7: UL3 at Speed Agree - Fault
Undertorque Detection only
active during Speed Agree
and drive output will shut
down on an OL3 fault.
8: UL3 at RUN - Fault
Undertorque Detection is
always active and drive output
will shut down on an OL3
fault.




L6-04

Overtorque
Detection Selection 2

0: Disabled
1: @SpdAgree - Alm
Detected during speed agree only.
2: At RUN - Alarm
Overtorque detection during running.
3: @SpdAgree - Flt
Detected during the speed agree only.
4: At RUN - Fault
Detected during running, and the inverter trips on OL4.

L6-04

Torque Detection
Selection 2

Additional selections:
5: UL4 at SpeedAgree -
Alarm Undertorque Detec tion
is only active during Speed
Agree and opera tion
continues after detection.
6: UL4 at RUN - Alarm
Undertorque Detection is
always active and operation
continues after detection.
7: UL4 at Speed Agree - Fault
Undertorque Detection only
active during Speed Agree
and drive out put will shut
down on an OL4 fault.
8: UL4 at RUN - Fault
Undertorque Detection is
always active and drive output
will shut down on an OL4
fault.

L8-10

Short-circuit
Protection Selection

0:Disabled
1: Enabled

L8-09

Output Ground Fault
Detection Selection

Changed parameter number
0: Disabled
1: Enabled

L8-10

Heatsink Cooling Fan
Operation Selection

New parameter
0: Fan On-Run Mode
1: Fan Always On

L8-11

Heatsink Cooling Fan
Operation Delay Time

New parameter

L8-12

Ambient Temperature
Setting

New parameter