Yaskawa GPD 515/G5 to F7 User Manual
Page 28
Product Transition Guide
Appendix 2- Parameter Differences
____________________________
PL.F7.02.TransitionGuide 6/5/06
Page 28 of 40
Yaskawa Electric America, Inc
GPD515/G5 Parameters
F7 Parameters
Parameter
No.
Name
(DigitalOperator
Display)
Setting or Selection
Parameter
No.
Name
(Digital Operator Display)
Remarks on
Setting or Selection
A1-01
Access Level
0: Operation Only
1: User Level
2: Quick-Start [Q]
3: Basic Level [B]
4: Advanced Level [A]
A1-01
Access Level Selection
0: Operation Only
1: User Level
Modified selection:
2: Advanced Level
B1-01
Reference Selection
0: Operator
1: Terminals
2: Communication Serial Com
3: Option PCB
4: EWS Reference from CP-717
b1-01
Reference Selection
Changed to:
4: Pulse Input
B1-02
Operation Method
Selection
0: Operator
1: Terminals
2: Communication Serial Com
3: Option PCB
4: EWSRun from CP-717
b1-02
Run Command
Selection
Removed selection 4:
4: EWSRun from CP-717
B1-04
Reverse Operation
Prohibit
0: Reverse Enabled
1: Reverse Disabled
b1-04
Reverse Operation
Selection
Additional function:
2: Exchange Phase - Change
direction of forward motor
rotation.
B3-01
Speed Search
Selection at Start
0: Disabled
1: Enabled
b3-01
Speed Search Selection
Modified selections:
0: Speed Estimation Speed
Search Disable
1: Speed Estimation Speed
Search Enable
2: Current Detection Speed
Search Disable
3: Current Detection Speed
Search Enable
—
—
—
b3-05
Speed Search Delay
Time
New Parameter
—
—
—
b3-10
Speed Search Detection
Compensation Gain
New Parameter
—
—
—
b3-14
Bi-directional Speed
Search Selection
New Parameter
0: Disable .
1: Enable
—
—
—
b5-15
Sleep Function Start
Level
New Parameter
—
—
—
b5-16
Sleep Delay Time
New Parameter
—
—
—
b5-17
PID Accel/Decel Time New Parameter
—
—
—
b5-18
PID Setpoint Selection
New Parameter
0:Disabled
1:Enabled
—
—
—
b5-19
PID Setpoint Value
New Parameter
B8-03
Energy -saving Mode
Selection
0:Disabled
1:Enabled
b8-01
Energy Saving Control
Selection
Changed Parameter No.
0: Disabled
1: Enabled
B8-04
Energy-saving
Control Gain
—
b8-02
Energy Saving Gain
Changed Parameter No.
B8-05
Energy-saving
Control Time
Constant
—
b8-03
Energy Saving Control
Filter Time Constant
Changed Parameter No.
—
—
—
b8-04
Energy Saving
Coefficient Value
New Parameter
—
—
—
b8-05
Power Detection Filter
Time
—
—
—
—
b8-06
Search Operation
Voltage Limit
—
C3-06
Output Voltage Limit
Operation Selection
0:Disabled
1:Enabled
C3-05
Output Voltage Limit
Opera tion Selection
Changed Parameter No.