480v heavy duty ratings (c6-01=0), F7 7 – Yaskawa GPD 515/G5 to F7 User Manual
Page 21

Product Transition Guide
Appendix 1 –Amps, Carrier , Overload, Dimensions, Heat Loss
____________________________
PL.F7.02.TransitionGuide 6/5/06
Page 21 of 40
Yaskawa Electric America, Inc
480V Heavy Duty Ratings (C6-01=0)
480V F7 “Heavy Duty” Setting (C6-01=0)
F
F
7
7
GPD515/G5 Model
NEC
HP
480V
NEC
Amps
F7
Model
CIMR-
F7U
Output
Amps
Heavy
Duty
Fc
kHz
Heavy
Duty
Overload
%
Heavy
Duty
GPD515/G5
Model CIMR-
G5U
Output
Amps
Fc
kHz
OL%
0.5 1.1
0.75 1.6
40P41
1.8 2 150 40P41
1.8 15 150
1 2.1
40P71 2.1 2 150
1.5 3
2 3.4
41P51
3.7 2 150
40P71
3.4 15 150
3 4.8
42P21 5.3 2 150 41P51
4.8 15 150
5.0 7.6 43P71 7.6 2 150
5.0 7.6 44P01 8.7 2 150
43P71
8 15
150
7.5 11 45P51 12.5 2 150 44P01
11.7 15 150
10 14 47P51 17 2 150 45P51
14 15
150
15 21 40111 24 2 150 47P51
21 12.5
150
20 27 40151 31 2 150 40111
27 12.5
150
25 34 40181 39 2 150 40151
34 10
150
30 40 40221 45 2 150 40181
41 10
150
40 52 40301 60 2 150 40221
52 8
150
50 65 40371 75 2 150 40301
65 8
150
60 77 40451 91 2 150 40371
80 6
150
75 96 40551 112 2 150 40451
96 6
150
100 124 40750 150 2 150 40551
128 6 150
125 156
40751
165 6 150
40900
180 2 150
40901-
195 5 150
150 180
41100
216 2 150 41101-
224 5 150
200 240 41320 260 2 150 41321-
270 5 150
250 302 41600 304 2 150 41601
302 5 150
300 361 41850 370 2 150
350 414
42200
450 2 150
400 477
42200
506 2 118
(1)
500 590 43000 675 2 120
(1)
43000
605 2 150
(1)
Heavy Duty overload current rating for model no. 42200 is 118% and 43000 is 120% of
rated output current for 60 seconds.