beautypg.com

Gpd515 g5, Product transition guide terminal comparison, Pl.f7.02.transitionguide page – Yaskawa GPD 515/G5 to F7 User Manual

Page 15: Of 40

background image

Product Transition Guide

Terminal Comparison

PL.F7.02.TransitionGuide Page

15

of 40

6/5/06

T/L3

S/L2

R/L1

S3 (H1-01)

S2

S1

SC

E(G)

S4 (H1-02)

S5 (H1-03)

S6 (H1-04)

S7 (H1-05)

SN

S+

R-

R+

S-

IG

F7

W/T3

V/T2

U/T1

MC

MB

MA

M2

M1

M4

M3

E(G)

(H4-01) FM

(H4-04) AM

AC

(H2-01)

(H2-02)

Modbus RTU

Communications

RS-485/422

19.2 Kbps

E

x

te

rn

a

l F

req

ue

nc

y

R

e

fe

re

n

c

e

MCCB

L3

L2

L1

3-Phase

Power

Supply

50/60Hz

Reverse Run/Stop

Foward Run/Stop

Multi-function

Digital Inputs 3-8

24VDC, 8 mA

M

Motor

Digital

Output 1

Fault

Contact

250VAC,

30VDC,

1A

Multi-

function

Digital

Outputs 2-4

250VAC,

30VDC, 1A

+

-

+

-

Multi-function

Analog Outputs 1-2

0 to +/-10VDC, 2mA

4-20mA, 500

+/-9 Bit Resolution

+/- 8% Accuracy

110

Ω

Terminating

Resistor

S8 (H1-06)

M6

M5

(H2-03)

Ω

Digital Inputs 1-2

24VDC, 8mA

SP 24VDC

+V +15VDC +/-10%, 20mA

A1 0 to +/-10VDC, 20 k *

A2 4 to 20mA, 250 *
[0 to +/-10VDC, 20k **]
Multi-function Analog Input 1 (H3-09)

AC

Ω

Ω

Ω

2k

Ω

2k

A3 0 to +/-10VDC, 20k *
Multi-function Analog Input 2 (H3-05)

Ω

RP 0 to 32kHz, 5 to 12VDC, 3k ***
Multi-function Pulse Input (H6-01)

S1

-V -15VDC +/-10%, 20mA

Ω

(H6-06) MP

Multi-function

Pulse Output

0 to 32kHz

9VDC @ 3k

+/-5% Accuracy

Ω

* +/-11 Bit Resolution, 0.2% Accuracy
** 11 Bit Resolution, 0.2% Accuracy
*** +/-5% Accuracy

+ 1

+ 2

+ 3

-

Shorting Bar Standard:
CIMR-F7U20P4 to 2018
CIMR-F7U40P4 to 4018

DC Reactor Standard:
CIMR-F7U2022 to 2110
CIMR-F7U4030 to 4300

U

X

GPD515

G5

F7

Note: Drawing size does not
represent actual drive size.