8 Option Fault Diagnostics

YASKAWA ELECTRIC TOBP C730600 29G 1000-Series Option JVOP-180 Installation Manual

55

LCD Operator

LED Operator

(V1000)

Description

oPr

Oper Disconnect

LCD Operator Option Connection Fault

oPr

Data should appear on the LED operator. By reconnecting the
option to the unit, data should also appear on option display.
An oPr fault will occur when both of the following conditions are
true:
Output is interrupted when the option is disconnected (o2-06 = 1).
The Run command is assigned to the option (b1-02/b1-16 = 0 and
LOCAL is selected).

Cause

Possible Solution

Option is not properly connected to the unit.

• Check the connection between the option and the unit.
• Replace the cable if damaged.
• Turn off the unit input power and disconnect the option.

Reconnect the option and reapply unit input power.

<1> Display will vary depending on operation status.