6 Basic Operation
YASKAWA ELECTRIC TOBP C730600 29G 1000-Series Option JVOP-180 Installation Manual
37
■
Example: Basic Operation
The following procedures are examples of converter operation using the option.
Note: Actual LCD display data varies based on converter parameter settings.
Procedure Example: RUN/STOP
Note: If b1-18 is not set to 0 (Operator), press
to set LOCAL.
Procedure
LCD Display
1. Apply main power to the converter. The DC Bus Voltage Reference appears after
the initial display on the option.
2. Press
to show the display for inputting the DC Bus voltage reference.
If b1-18 is not set to 0 (Operator), press
to set LOCAL.
3. Press
until the DC bus voltage
reference changes to the desired voltage.
4. Press
to set the output voltage.
RE
LO
- MODE -
U1-51= 0330V
U1-52= 295V
U1-53= 0.0A
DRV
Volt Ref
Rdy
LSEQ
LREF
RE
LO
←
→
-MONITR-
Volt Ref
U1-51=
0
330V
㧔
300㨪360㧕
̌
330V̍
DRV Rdy
F1
F2
←
→
-MONITR-
Volt Ref
U1-51= 320V
㧔
300㨪360㧕
̌
330V̍
DRV Rdy
Entry Accepted