Fault and minor fault contents, 10 cc-link code numbers – Yaskawa 1000 Series Drive Option - CC-Link Technical Manual User Manual
Page 29

10 CC-Link Code Numbers
YASKAWA ELECTRIC
SIEP C730600 44A YASKAWA AC Drive-Option Card CC-Link Technical Manual
29
◆
Fault and Minor Fault Contents
Table 21 Fault Contents
0036H
PID output
Units: 0.1%
1000H
Number of pulse 1 speed detection
1001H
Number of pulse 2 speed detection
1002H
Cumulative operation time
1003H
Watt-hour output (lower digits)
1004H
Watt-hour output (upper digits)
1010H
Alarm code
1011H
Fault code
1012H
Reserved
1013H
Fault contents 1
1014H
Fault contents 2
1015H
Fault contents 3
1016H
Fault contents 4
1017H
Fault contents 5
101CH
CPF contents 1
101DH
CPF contents 2
101EH
CPF contents 3
101FH
Alarm contents 1
1020H
Alarm contents 2
1021H
Alarm contents 3
1022H
Alarm contents 4
1023H
Alarm contents 5
1027H
Output frequency when fault occurred
1028H
Output frequency when fault occurred
1029H
Output voltage when fault occurred
102AH
Total operation time when fault occurred
Fault and Minor Fault Contents on page 29
for information on fault and minor fault contents.
Extended Command Code
(Monitor Code)
Fault Name
Fault Code (U2, U3)
BIT
120H
(1013H)
Fault contents 1
0
Reserved
–
1
Undervoltage (Uv1)
0002H
2
Control power supply undervoltage (Uv2)
0003H
3
Softcharge circuit fault (Uv3)
0004H
4
Load short-circuit (SC)
0005H
5
Reserved
–
6
Overcurrent (oC)
0007H
7
Overvoltage (ov)
0008H
8
Heatsink overheat (oH)
0009H
9
Heatsink overheat (oH1)
000AH
A
Motor overload (oL1)
000BH
B
Drive overload (oL2)
000CH
C
Overtorque detection 1 (oL3)
000DH
D
Overtorque detection 2 (oL4)
000EH
E
Dynamic braking transistor (rr)
000FH
F
Braking resistor overheat (rH)
0010H
Monitor Code
Name
Comments