8 CC-Link Data Table

YASKAWA ELECTRIC

SIEP C730600 44A YASKAWA AC Drive-Option Card CC-Link Technical Manual

19

8

CC-Link Data Table

Remote I/O

The drive takes up a single station address in the buffer memory or the PLC. The table below shows the drive I/O as seen from the PLC side.

Note: Refer to the PLC’s programming manual for information on the PLC’s buffer memory.

PLC

Drive

Table 9 Remote I/O Table (PLC

Drive)

Note: 1. If making frequent setting changes, use RYD (Frequency Reference 1 flag) for setting the register. Using RYE (Frequency Reference 2 flag) too often can shorten the

performance life of the drive's internal memory.

2. Although RYE and RYF are triggered by the rising edge of the signal, they are otherwise enabled depending on the value that is input.

When switching between monitors using RYC (Monitor Reference), RYC needs to be turned off and then back on again after the monitor code has been changed.

Signal

Name

Description

Default

RY0

Forward Run

ON: Forward Run Command, OFF: Stop

RY1

Reverse Run

ON: Reverse Run Command, OFF: Stop

RY2

Terminal S3 Function

Multi-function input: H1-03

(H1-03 = 24: External Fault)

RY3

Terminal S4 Function

Multi-function input: H1-04

(H1-04 = 14: Fault Reset)

RY4

Terminal S5 Function

Multi-function input: H1-05

(H1-05 = 3: Multi-Step Speed 1)

RY5

Terminal S6 Function

Multi-function input: H1-06

(H1-06 = 4: Multi-Step Speed 2)

RY6

Terminal S7 Function

Multi-function input: H1-07

(H1-07 = 6: Jog Reference)

RY7

Terminal S8 Function

Multi-function input: H1-08

(H1-08=8, baseblock command)

RY8

Reserved

RY9

Drive Output Interrupt

ON: Motor coasts to stop.
OFF: Drive will begin operating as soon as a Run command is given.

RYA

External Fault

ON: External Fault Input (EF0)

RYB

Motor Revolutions / Output
Frequency Switch

Data contents for the remote register RW

R1

switches between motor revolutions and

output frequency.

Motor rotations are displayed
when not in V/f or OLV for PM.

RYC

Monitor Reference

ON: Monitor data specified in the monitor code is set to remote register RW

R0

.

RYD

Frequency Reference 1

Frequency set to remote register RW

W1

becomes the operating frequency for the drive.

RYE

Frequency Reference 2

Sets the frequency in the remote register RW

W1

to parameter d1-01 (Frequency Reference

1) and as the drive’s main frequency reference at the same time.

Note: If the frequency reference is set to be provided by the operator

(i.e, b1-01 = 0), then switching on RYE changes the frequency

reference.

All parameter settings are saved
when this flag is switched on.
Triggered by the rising edge of
the signal.

RYF

Command Code Execute Request

Request to execute the command code.

Triggered by the rising edge of
the signal.

RY10 to 13

Reserved

RY14

Terminal S1 Function

Multi-function input: H1-01

Function is disabled when for the
Forward Run Command (H1-01
= 40).

RY15

Terminal S2 Function

Multi-function input: H1-02

Function is disabled when for the
Reverse Run Command (H1-02 =
41).

RY16 to 19

Reserved

RY1A

Fault Reset

Resets a drive fault

RY1B to 1F

Reserved