beautypg.com

Fault led display on cc-link option side, 9 troubleshooting – Yaskawa 1000 Series Drive Option - CC-Link Technical Manual User Manual

Page 23

background image

9 Troubleshooting

YASKAWA ELECTRIC

SIEP C730600 44A YASKAWA AC Drive-Option Card CC-Link Technical Manual

23

Minor Faults and Alarms

Fault LED Display on CC-Link Option Side

Checking LED Operation

Table 15 LED Display

Note: If communication stops while the drive is running, check the following:

• Is the CC-Link properly installed?

• Is the CC-Link communication line connected to the CC-Link Option correctly? Is it loose?

• Is the PLC program working? Has the PLC CPU stopped?

• Did a momentary loss in power interrupt communications?

Operator Display

Fault Name

oFb02

CC-Link Option Fault (CN5-B)
Two of the same option cards are connected at the same time.

Cause

Possible Solution

Option cards AI-A3 or D1-A3 were connected to the CN5-
B port while an option card was already connected to CN5-
A.

⇒ Only one type of option input card AI-A3 or DI-A3 can be connected to the drive. Only this option card for CANopen can be
connected to CN5-A.

Operator Display

Fault Name

oFc00

CC-Link Option Fault (CN5-C)
Non-compatible option card is connected.

Cause

Possible Solution

Non-compatible option connected to the drive.

⇒ Connect the correct option card to CN5-A.

Operator Display

Fault Name

oFc02

CC-Link Option Fault (CN5-C)
Two of the same option cards are connected at the same time.

Cause

Possible Solution

Option cards AI-A3 or D1-A3 were connected to the CN5-
C port while an option card was already connected to CN5-
A.

⇒ Only one type of option input card AI-A3 or DI-A3 can be connected to the drive. Only this option card for CANopen can be
connected to CN5-A.

Operator Display

Minor Fault Name

AEr

Station Address Error
CC-Link Option is set to an address outside the allowable setting range.

Cause

Possible Solution

Minor Fault

(H2-†† = 10)

Address outside the specified address range

⇒ Set F6-10 to an address within the specified range.

YES

Operator Display

Minor Fault Name

CALL

Serial Communication Transmission Error
Communication has not yet been established.

Cause

Possible Solution

Minor Fault

(H2-†† = 10)

Communication wiring is faulty, there is a short circuit, or
something is not connected properly.

Check for wiring errors.

⇒ Correct the wiring.

⇒ Remove and ground shorts and reconnect loose wires.

YES

Programming error on the master side

⇒ Check communications at start-up and correct programming errors.

Communication circuitry is damaged.

Perform a self-diagnostics check.

⇒ Replace the drive if the fault continues to occur.

L.RUN

Switches on when data is being received normally. Turns off when the receive data is interrupted.

SD

Lights whenever the drive is sending data.

RD

Lights whenever the drive is receiving data.

L.ERR