Minor Faults and Alarms
◆
Fault LED Display on CC-Link Option Side
■
Checking LED Operation
Table 15 LED Display
Note: If communication stops while the drive is running, check the following:
• Is the CC-Link properly installed?
• Is the CC-Link communication line connected to the CC-Link Option correctly? Is it loose?
• Is the PLC program working? Has the PLC CPU stopped?
• Did a momentary loss in power interrupt communications?
Operator Display
Fault Name
oFb02
CC-Link Option Fault (CN5-B)
Two of the same option cards are connected at the same time.
Cause
Possible Solution
Option cards AI-A3 or D1-A3 were connected to the CN5-
B port while an option card was already connected to CN5-
A.
⇒ Only one type of option input card AI-A3 or DI-A3 can be connected to the drive. Only this option card for CANopen can be
connected to CN5-A.
Operator Display
Fault Name
oFc00
CC-Link Option Fault (CN5-C)
Non-compatible option card is connected.
Cause
Possible Solution
Non-compatible option connected to the drive.
⇒ Connect the correct option card to CN5-A.
Operator Display
Fault Name
oFc02
CC-Link Option Fault (CN5-C)
Two of the same option cards are connected at the same time.
Cause
Possible Solution
Option cards AI-A3 or D1-A3 were connected to the CN5-
C port while an option card was already connected to CN5-
A.
⇒ Only one type of option input card AI-A3 or DI-A3 can be connected to the drive. Only this option card for CANopen can be
connected to CN5-A.
Operator Display
Minor Fault Name
AEr
Station Address Error
CC-Link Option is set to an address outside the allowable setting range.
Cause
Possible Solution
Minor Fault
(H2- = 10)
Address outside the specified address range
⇒ Set F6-10 to an address within the specified range.
YES
Operator Display
Minor Fault Name
CALL
Serial Communication Transmission Error
Communication has not yet been established.
Cause
Possible Solution
Minor Fault
(H2- = 10)
Communication wiring is faulty, there is a short circuit, or
something is not connected properly.
Check for wiring errors.
⇒ Correct the wiring.
⇒ Remove and ground shorts and reconnect loose wires.
YES
Programming error on the master side
⇒ Check communications at start-up and correct programming errors.
Communication circuitry is damaged.
Perform a self-diagnostics check.
⇒ Replace the drive if the fault continues to occur.
L.RUN
Switches on when data is being received normally. Turns off when the receive data is interrupted.
SD
Lights whenever the drive is sending data.
RD
Lights whenever the drive is receiving data.
L.ERR
Lights when a CRC or abort error occurs.