7 Basic Functions

YASKAWA ELECTRIC

SIEP C730600 44A YASKAWA AC Drive-Option Card CC-Link Technical Manual

17

7

Basic Functions

This interface allows the drive to be connected to a CC-Link network as a remote device, making it possible to operate, adjust settings, and monitor

the operation status of the drive using the PLC program. Both bit and word data cyclic transmission are available, and high speed communication up

to 10 Mbps is possible.
Below is a description of the basic CC-Link functions that can be performed by the PLC.

Note: Set parameters when operating the drive from a PLC. For instructions, see

CC-Link Option Drive Parameters on page 16

.

Switching Between Command/Reference Sources

The Run command, Stop command, and the frequency reference can be entered directly from the operator or given from a separate control device.
To use a separate control device to issue the Run command and frequency reference, the drive needs to be set so that it accepts theses commands

from an external source.

Selecting an External Source

Follow the directions below set the drive up to accept commands from an external controller.

• Using Parameters to Select the Command/Reference Source

• Using the External Terminals to Switch the Command/Reference Source

• Using a PLC as the Command/Reference Source

Using Parameters to Select the Command/Reference Source

Selecting the Run Command Source

Set b1-02 (Run Command Selection) to 3 ("Option PCB").

Selecting the Source of the Frequency Reference

Set b1-01 (Frequency Reference Selection) to 3 (“Option PCB”).

Using the External Terminals to Switch the Command/Reference Source

Selecting the Run Command Source 2

Set b1-16 (Run Command Source 2) to 3 (“Option card”).

Selecting the Source of the Frequency Reference 2

Set b1-15 (Frequency Reference Source 2) to 3 (“Option card”).

Selecting the Run Command and Frequency Reference Source

By setting one of the multi-function input terminals S1 through S8 to supply auxiliary reference (H1-01 to H1-08 = 2), then the frequency reference

set to b1-15 and the run command source set to b1-16 will become enabled.

Using a PLC as the Command/Reference Source

Using Parameters to Switch Sources

Note: By setting H1-†† = 2, then parameters b1-15 and b1-16 will become enabled when that terminal is switched on.

• Selecting the Run Command Source

Send write data “3” for command code 2181H to the drive.
The setting for parameter b1-02 changes to “3”.

• Frequency Reference Source Selection

Send write data “3” for command code 2180H to the drive.
The setting for parameter b1-01 changes to “3”.

Using NetRef and NetCtrl

It is also possible to change the source of the frequency reference and the Run command using remote register RW

W2

command code 00FBH.

If the power is shut off, however, the drive will use the original setting for the command/reference source once the power is turned back again. This

method should therefore only be used when briefly switching between command/reference sources.