4 precision of measured value acquisition, Precision of measured value acquisition – SMA SB 4200TL Multi-String User Manual
Page 49
SMA
Technologie AG
Technical Documentation
Operating Instructions
SB4200-12:FE4804
Page 49
6.4.4 Precision of Measured Value Acquisition
Acquisition of measured values always is imprecise within a certain margin. The
measued values acquired by the Sunny Boy 4200TL Multi-String are required for its
system management and control of current to be fed to the grid. This is why measured
values of the Sunny Boy 4200TL Multi-String must be reproducible. The maximum er-
ror of measured value acquisition is specified for an ambient temperature T
U
of
25°C. A temperature coefficient failure must be accounted for with other ambient
temperatures.
Table 6.3: Measured value acquisition of the Sunny Boy 4200TL Multi-String
Physical
variable
Unit
Measurement
range
Resolutio
nof
display
Resolution of
measuremen
t
Max. failure
(of final
value,
T
U
=25°C)
Input voltage
UPV1-3 [V]
0 ... 800 V
1 V
0.78 V
±2 %
Input current
IPV1-3
[mA]
0 ... 10000 mA
1 mA
9.8 mA
±2 %
Grid voltage
UAC [V]
180 ... 278 V
eff
1 V
0.27 V
eff
±1 %
Grid current
IAC [mA]
0 ... 26.5 A
eff
1 mA
13 mA
eff
±2 %
Grid frequency
fAC [Hz]
45 ... 55 Hz
0.01 Hz
0.01 Hz
±0.1 %
Power fed to
grid
PAC [W]
0 ... 7367 W
1 W
1 W
±3 %
Energy fed to
grid
E [kWh]
0 ... 4.29*10
9
Wmin
1 Wmin
20 Wmin
±3 %
Operating hours
h [h]
0 ... 4.299*10
9
s
1 s
375 ns
±0.1 %