Device Description

Operating Instructions

SB4200-12:FE4804

Page 21

Grid Impedance too High

When this failure occurs, the yellow failure LED is on for five seconds and then starts
the blinking code by staying off for three seconds and then blinking three times in
short intervals. The code is sent three times.

If the failure persists, the signal starts from the beginning.

The Sunny Boy has detected a failure as the grid impedance values are out of per-
missible range. If the inverter switches off frequently during grid monitoring because
of the above failure, the reason might be that grid impedance is too high. A qualified
electrician can normally solve this problem by increasing the cross-section of the grid
cable. Other actions are possible as well. Any modifications of the operating para-
meters require the explicit permission of the public utility company.

5 s

3 s

1 s

LED on

LED off

Yellow LED is blinking 3
times in short intervals.

The signal is repeated 3 times and
then starts from the beginning.