beautypg.com

SMA SB 4200TL Multi-String User Manual

Page 28

background image

Device Description

SMA

Technologie AG

Page 28

SB4200-12:FE4804

Operating Instructions

Messages of the Sunny Display in Case of a Failure

In case of a failure the Sunny Display switches to „Failure“ and the background illu-
mination is activated.

The bottom line indicates the type of failure for 5 se-
conds.

Failures that result from a specific value that e.g. ex-
ceeds a limiting are specified with the value that
caused the failure as well as the current value.

The normal operating data are displayed after 5 se-
conds.

The display starts from the beginning again in case the failure is still present. Chapter
6.4 "Measurement Channels and Messages" (page 44) gives more detailed informa-
tion concerning the failure messages.

“Error ROM“ indicates that the Sunny Boy has detec-
ted a defective firmware in the EEPROM. Contact
SMA in order to remove this failure.

Indication of DC Overvoltage

A too high voltage on the input (DC) side is indicated
with a blinking background illumination and the dis-
play shown on the side.

Check the input voltage and your module configuration before you reconnect the DC
voltage to the Sunny Boy again!

Disconnect the Sunny Boy from the supply voltage immediate-
ly! The Sunny Boy can otherwise be severely damaged!

Indication of a failure

and failure type

Error
Uac-Bfr

Display of the value that caused the

failure and the current value

at: 261V
present: 245V

Indication of defective firmware

Error
ROM

Indication of an overvoltage on one

of the DC input connectors

!PV-Overvoltage!
!DISCONNECT DC !