Device Description

SMA

Technologie AG

Page 22

SB4200-12:FE4804

Operating Instructions

Input Voltage (PV Generator) too High

When the failure occurs, the yellow failure LED is on for five seconds and then starts
the blinking code by staying off for three seconds and then blinking four times in short
intervals. The code is sent three times.

The Sunny Boy indicates that the input voltage is too high. The voltage of the PV ge-
nerator exceeds 750 V DC the respectively admissible voltage!

Immediately disconnect the PV generator from the Sunny Boy
4200TL Multi-String. Too high voltage may lead to irrepairable
damages!

Have your installer examine your plant configuration.

5 s

3 s

1 s

1 s

1 s 1 s

LED on

LED off

Yellow LED is blinking 4
times in short intervals.

The signal is repeated 3 times and
then starts from the beginning.