5 Assembly

5.1 Open SMA DC-Disconnect.

1. Disconnect the AC switch and make sure it cannot be switched on.
2. Turn the DC disconnector to the "Off" position and

wait 5 minutes until the capacitors of the inverter
are discharged.
☑ The inverter is disconnected on the AC and DC

sides.

3. Loosen the screws on the enclosure of the SMA DC-

Disconnect (turn the screws in a counterclockwise
direction). Leave the screws and tab washers on the
cover.

4. Remove the cover of the SMA DC-Disconnect

towards the front.

5. Place the cover to one side.

☑ The SMA DC-Disconnect is open.

WARNING

High voltages in the inverter. Death or serious injuries.

• Before working on the SMA DC-Disconnect, disconnect the AC switch and make sure

it cannot be switched on.

• Disconnect the multi-function relay power supply.
• Set the DC disconnector of the SMA DC-Disconnect to the "Off" position.
• Wait 5 minutes before opening the cover of the SMA DC-Disconnect, until the

capacitors of the inverter are discharged.