Preparations for the RS485-Quick Module

SMA America, LLC

18

RS485-QM-IA-eng-IUS111610

Installation Guide

4.4 Terminating the RS485 Bus

You must set the termination only on the inverter that is connected to the end of the RS485 bus. When
the RS485-Quick Module is delivered, the resistor for termination is located in the left spring-type
terminal. If the resistor (wire resistor: 120 Ohms) is no longer connected, proceed as described in this
chapter:

1. Flip up the flap of the RS485-Quick Module and lift

the cover until it snaps into place.

2. Open spring-type terminals 2 and 7 of the left-hand

connector.

3. Connect the resistor to spring-type terminals

2 and 7.

4. Close the spring-type terminals.

5. Close the cover of the RS485-Quick Module and

fold back the flap so that it snaps into place.

☑ The RS485 bus is terminated.