7.4.4 Precision of Measured Value Acquisition
Acquisition of measured values is always more or less imprecise. The measued values
acquired by the Sunny Boy 3300TL are required for its system management and con-
trol of current to be fed into the grid. This is why measured values of the Sunny Boy
3300TL must be reproducible. The maximum error of measured value acquisition is
specified for an ambient temperature T
U
of 25°C. A temperature coefficient failure
must be accounted for with other ambient temperatures.
Physical
variable
Unit
Measurement
range
Resolu-
tion of
display
Resolution of
measure-
ment
Max. failure
(of final
value,
T
U
=25°C)
Input voltage
UPV [V]
0 ... 800 V
1 V
0.78 V
±2 %
Input current
IPV [mA]
0 ... 10000 mA
1 mA
9.8 mA
±2 %
Grid voltage
UAC [V]
180 ... 278 V
eff
1 V
0.27 V
eff
±1 %
Grid current
IAC [mA]
0 ... 26.5 A
eff
1 mA
13 mA
eff
±2 %
Grid frequency
fAC [Hz]
45 ... 55 Hz
0.01 Hz
0.01 Hz
±0.1 %
Current power
fed to grid
PAC [W]
0 ... 7367 W
1 W
1 W
±3 %
Total energy fed
to grid
E [kWh]
0 ... 4.29*10
9
Wmin
1 Wmin
20 Wmin
±3 %
Operating hours
h [h]
0 ... 4.299*10
9
s
1 s
375 ns
±0.1 %