7.4.4 Precision of Measured Value Acquisition

Acquisition of measured values is always more or less imprecise. The measued values
acquired by the Sunny Boy 3300TL are required for its system management and con-
trol of current to be fed into the grid. This is why measured values of the Sunny Boy
3300TL must be reproducible. The maximum error of measured value acquisition is
specified for an ambient temperature T

U

of 25°C. A temperature coefficient failure

must be accounted for with other ambient temperatures.

Physical
variable

Unit

Measurement

range

Resolu-

tion of

display

Resolution of

measure-

ment

Max. failure

(of final

value,

T

U

=25°C)

Input voltage

UPV [V]

0 ... 800 V

1 V

0.78 V

±2 %

Input current

IPV [mA]

0 ... 10000 mA

1 mA

9.8 mA

±2 %

Grid voltage

UAC [V]

180 ... 278 V

eff

1 V

0.27 V

eff

±1 %

Grid current

IAC [mA]

0 ... 26.5 A

eff

1 mA

13 mA

eff

±2 %

Grid frequency

fAC [Hz]

45 ... 55 Hz

0.01 Hz

0.01 Hz

±0.1 %

Current power
fed to grid

PAC [W]

0 ... 7367 W

1 W

1 W

±3 %

Total energy fed
to grid

E [kWh]

0 ... 4.29*10

9

Wmin

1 Wmin

20 Wmin

±3 %

Operating hours

h [h]

0 ... 4.299*10

9

s

1 s

375 ns

±0.1 %