Page 46

background image

Technical Documentation

SMA

Technologie AG

Page 42

SB3300TL-11:FE1905

Operating Instructions

7.4.3 Sunny Boy 3300TL Operating Parameters

Any unauthorized modifications of the operating parameters
can

• result in serious injuries or casualties due to altered internal

safety precautions within the Sunny Boy

• void the operating permission of the Sunny Boy
• void the warranty of the Sunny Boy.

Never change the operating parameters without explicit per-
mission and instructions!

Name Unit

Range

Default

Description

E_Total

kWh

0

...

200000

Total energy yield (E_Total) and total
operating hours (h_Total) of the inverter.
Changing the value can be necessary when a
Sunny Boy is exchanged and you wish to
match the previously acquired data.

h_Total

h

0 ... 200000

Usoll-Konst /
Vconst-Setpoint

V

0

...

750

290

PV setpoint voltage for constant voltage
operation for String A. These parameters are
only important in case the parameter
„Operating Mode“ is set to „U-konst“.

NiTest/
impedance test

0

/

1

1

Activates (1) and deactivates (0) the
automatic failure current measurement. This
parameter only takes effect when the Sunny
Boy was deactivated (by disconnecting from
the AC utility) or set to operating mode
„Stop“.

Uac-Min

V

180 ... 300

198

Lower (Uac-Min) and upper (Uac-Max) limit of
permissible AC voltage (Anti-Islanding)

Uac-Max

V

180 ... 300

260

Fac-Delta-

Hz

0 ... 4.5 (0.19)

0.19

Maximal frequency above (Fac-Delta+) and
below (Fac-Delta-) 50 Hz grid frequency
before anti-islanding is triggered

Fac-Delta+

Hz

0 ... 4.5

0.19

dFac-MAX

Hz/s

0.005

...

4.0

0.25

Maximal „rate of change of frequency“
before anti-islanding tis triggered

dZac-MAX

mOhm

0 ... 2000

350

Maximal „rate of change of grid impedance“
before anti-islanding is triggered

Riso-Min

kOhm

1000 ... 30000

1000

Minimum insulation resistance

Betriebsart/
Operating Mode

MPP/

Ikonst/

UKonst/

Stop

MPP

Operating Mode of the Sunny Boy:
MPP: Maximum Power Point
Ukonst: Constant Voltage Mode (Setpoint
defined in „Usoll-Konst“)
IKonst: Experimental mode/special
applications
Stop: Disconnection from utility, no operation