SMA SB 3300TL User Manual

Page 24

background image

Device Description

SMA

Technologie AG

Page 20

SB3300TL-11:FE1905

Operating Instructions

Discharge Current too high

When the failure occurs, the yellow failure LED is on for five seconds and then starts
the blinking code by staying off for three seconds and then blinking six times in short
intervals. The code is sent three times. If the failure persists, the signal starts from the
beginning.

The discharge current of the inverter and the PV-generator exceeds 95 mA. The de-
vice immediately interrupts feeding operation when this limit has been exceeded and
then automatically reconnects to the grid.

The discharge current depends on the capacity of the PV-generator towards ground.
This depends on the way how the modules are installed as well as on weather condi-
tions. It is therefore normal that this value varies over time.

This failure can also occur when the PE connection (protective ground) is defective.

Should the Sunny Boy 3300TL indicate this failure often, please ask the installer of
your PV-plant to find the cause of the high fault current.

5 s

3 s

1 s

1 s

1 s 1 s 1 s 1 s

LED on

LED off

Yellow LED is blinking 6
times in short intervals.

The signal is repeated 3 times and
then starts from the beginning.