Drastic change of differential current – SMA SB 3300TL User Manual

Page 25

background image

SMA

Technologie AG

Device Description

Operating Instructions

SB3300TL-11:FE1905

Page 21

Drastic Change of Differential Current

When the failure occurs, the yellow failure LED is on for five seconds and then starts
the blinking code by staying off for three seconds and then blinking seven times in
short intervals. The code is sent three times. If the failure persists, the signal starts from
the beginning.

The Sunny Boy 3300TL detected a drastic change of differential current and immedi-
ately interrupted its connection to the grid. The all-pole sensitive differential current
monitoring integrated in the inverter monitors the discharge current to ground from
the grid connection of the inverter to the PV-generator. This additional personnel safe-
ty concept reacts to a change of differential current of IDN > 30 mA and disconnects
the inverter from grid within 0.2 seconds.

5 s

3 s

1 s

1 s

1 s 1 s 1 s 1 s

LED on

LED off

Yellow LED is blinking 7
times in short intervals.

The signal is repeated 3 times and
then starts from the beginning.