Connecting of AC output

Please follow the steps below:

1. Disconnect the grid (switch off the circuit breaker), secure it

against accidental reactivation and ensure that it is discon-
nected.

2. The AC connector is a round socket that is suitable to take

different cable diameters. A PG13.5 and a PG16 cable seal
are included with the AC connection socket. Check which
size is suitable for your AC connection cable.

3. Strip the insulation off the ends of the cable and connect the

cable to the AC socket as shown below.

4. Push the rubber ring into the fastening case.

5. Put the cable through the PG13.5 or 16 cable seal. Put the

cable through the fastening case with the rubber ring and
through the socket tube.

6. Connect the wires of the AC cable as follows:

• Protective Earth (PE) to the terminal with the „ ground“ sym-

bol.

• Neutral wire to the terminal marked with „ 1“
• Phase L to the terminal marked with „ 2“
• The terminal marked with „ 3“ is not used.
7. Make sure that all wires are firmly connected.

8. Push the socket tube firmly onto the socket.

Before opening the Sunny Boy check

whether the AC output is safely isola-

ted from supply!