Requirements for the Installation

SB2800i-11:SE0504

SMA Regelsysteme GmbH

13

4.3 Requirements: Grid 230 V~ (AC)

The relevant technical regulations as well as specific requirements
defined by the local public utility have to be complied with.

The terminals of the Sunny Boy 2800i are suitable for cables with
a cross-section of up to 2.5 mm². The Sunny Boy is connected with
three wires (L, N, PE).

Each connection to a Sunny Boy 2800i must be
equipped with a separate circuit breaker 16 A.
No other consumers may be connected to the
cable.

The Sunny Boy has to be connected

to grid with three wires!

No additional consumers may be

connected between the Sunny Boy

and the fuse!