Table 4.1: minimum clearance – SMA SB 2800i Installation User Manual
Page 12

Requirements for the Installation
Installation Guide
10
SMA Regelsysteme GmbH
SB2800i-11:SE0504
Please make sure there is a sufficient space for heat dissipation!
In a normal environment the following clearance should be
provided for a single Sunny Boy 2800i
Table 4.1: Minimum clearance
If you want to install several Sunny Boy 2800i side by side on the
same level, pay attention to the minimum distance between them.
If there is not enough space between the devices, the left Sunny
Boy will reduce the yield of the PV plant because of the
incomming air temperature.
The minimum space between two Sunny Boy 2800i has to be
40 cm.
Minimum clearance
Lateral
20 cm
Top
20 cm
Bottom
20 cm
Front
5 cm
Pay attention to the required minimum
clearance for the Sunny Boy 2800i
Two or more Sunny Boy 2800i
may not be mounted directly to
each other.
- SUNNY PORTAL (75 pages)
- SB 2.5-1VL-40 (60 pages)
- SB 2.5-1VL-40 Service Manual (36 pages)
- SB 240 (78 pages)
- FLX Pro 17 (12 pages)
- FLX Series GSM Option Kit (48 pages)
- FLX Series Sensor Interface Option (51 pages)
- FLX Series PLA Option (62 pages)
- FLX Series (248 pages)
- 25000TL (52 pages)
- 25000TL Installation (40 pages)
- 25000TL Service Manual (46 pages)
- CBL-DC-CMB8-10 (24 pages)
- 25000TL Quick Installation Guide (36 pages)
- STP 60-10 Replacing a Defective Fan (12 pages)
- STP 60-10 Replacing Defective Surge Arresters (12 pages)
- Webconnect Systems in SUNNY PORTAL (69 pages)
- STP 12000TL (68 pages)
- STP 60-US-10 Installation (232 pages)
- 485 Data Module Type B (24 pages)
- STP 12000TL Quick Installation Guide (28 pages)
- 1000-US (52 pages)
- STP 24000TL-US (78 pages)
- STP 17000TL (60 pages)
- STP 20000TL (2 pages)
- SB 6000TL Service Manual (46 pages)
- MULTIFUNCTION RELAY (32 pages)
- SB 5000TL (60 pages)
- SB 5000TL Quick Installation Guide (32 pages)
- FANKIT01-10 (24 pages)
- SB 7700TL-US (28 pages)
- FANKIT02-10 (24 pages)
- SB 7700TL-US Installation (96 pages)
- SUNNY MINI CENTRAL (48 pages)
- DC Disconnect Switch For SB 3800-U (32 pages)
- SB 4000-US (100 pages)
- DB-DC-DISCON (4 pages)
- SB 3800-U (86 pages)
- POWER BALANCER (28 pages)
- SB 8000-US (104 pages)
- SB 11000TL‑US (40 pages)
- SMC 11000TL (24 pages)
- SBCBTL6 (36 pages)
- SB 11000TL‑US Installation (92 pages)
- SMC 11000TL Installation (96 pages)