5.8 Connecting a Generator (Optional)

Cable Requirements

The cable type and laying method must be suitable for the application and use location.

NOTICE!
Destruction of the cables through faulty cable design.

• Select the required cable cross-section according to the nominal power of the

generator.

• The design of the output fuse of the generator may affect the design of the cable to

the PV system.

• If the generator does not have an output fuse, implement the cable connection to the

Automatic Switch Box in a ground-fault proof and short-circuit proof manner. As an
alternative - especially for long cable distances - you can install an additional fuse
box close to the generator.

• Install fuses and protect the cable to the generator against short-circuit currents from

the grid and against overload.

Cable end sleeves
When using fine-wired cables, use cable end sleeves as well.
This only applies for the cable connected to the "F6 Generator" fuse element.

Cable cross section