SMA CLUSTER CONTROLLER User Manual
Page 32

Parameter
Explanation
Start setpoint active power limita-
tion
Lower limit for the setpoint for the active power limitation re-
lated to the inverter parameter Set active power limit or
Pmax
End setpoint active power limita-
tion
Upper limit for the setpoint for the active power limitation re-
lated to the inverter parameter Set active power limit or
Pmax
For reactive power setpoint in %:
Start setpoint reactive power
Lower limit for the setpoint for the reactive power setpoint re-
lated to the inverter parameter Set active power limit or
Pmax
For reactive power setpoint in %:
End setpoint reactive power
Upper limit for the setpoint for the reactive power setpoint re-
lated to the inverter parameter Set active power limit or
Pmax
For setpoint cos Phi:
Cos Phi start setpoint
Lower limit for the setpoint of the displacement power factor
cos φ
For setpoint cos Phi:
Cos Phi end setpoint
Upper limit for the setpoint of the displacement power factor
cos φ
For setpoint cos Phi:
Excitation type
Direction of phase shift
4 User Interface of the Cluster Controller
SMA Solar Technology AG / SMA America, LLC
User Manual
ClusterController-BA-en-14
32