beautypg.com

SMA MC-Box 6.3 User Manual

Page 43

background image

SMA Solar Technology AG

12  Technical Data of the Multicluster Box 12.3

Operating Manual

MC-BOX-6_12-BE-en-20

43

Generator Connection

Grounding Connection

Mechanical Data

Ambient Conditions

Protection Rating

Maximum torque of stud terminal

10 Nm to 20 Nm

Maximum torque of the fuse switch-disconnector

14 Nm

Maximum connectable conductor cross-section

120 mm²

Maximum fuse link

160 A

Fuses

LV/HRC size 00

Quantity

1 (three-phase)

AC input current

3 x 160 A

Rated grid input power

110 kW

Diameter of stud terminal for connecting N and grounding
conductor

10 mm

Diameter of the screws at the fuse switch-disconnector for
connecting L1, L2 and L3

8 mm

Maximum torque of stud terminal

10 Nm to 20 Nm

Maximum torque of the fuse switch-disconnector

14 Nm

Maximum connectable conductor cross-section

120 mm²

Maximum fuse link

160 A

Fuses

LV/HRC size 00

Stud terminal diameter

10 mm

Maximum torque

10 Nm to 20 Nm

Maximum connectable conductor cross-section

120 mm²

Width x height x depth

1,000 mm x 1,400 mm x 300 mm

Weight

110 kg

Ambient temperature

–25°C to +50°C

Humidity

0% to 100%

Protection class (in accordance with DIN EN 60529)

IP55