12 technical data of the multicluster box 12.3 – SMA MC-Box 6.3 User Manual
Page 42
12 Technical Data of the Multicluster Box 12.3
SMA Solar Technology AG
42
MC-BOX-6_12-BE-en-20
Operating Manual
12 Technical Data of the Multicluster Box 12.3
General Data
Sunny Island Connection
PV System Connection
Load Connection
Number of line conductors
Three-phase
Nominal voltage (range)
230 V / 400 V
(172,5 V to 250 V / 300 V to 433 V)
Nominal frequency (range)
50 Hz (40 Hz to 70 Hz)
Permitted grid configuration
TN
Mounting type / Installation type
Upright on a base
Quantity
12
Rated current
3 x 104.3 A
Rated power
72 kW
Maximum connectable conductor cross-section
16 mm²
Fuses
12 x circuit breaker C32A
Quantity
1 (three-phase)
Rated current
3 x 160 A
Rated power
110 kW
Diameter of stud terminals
10 mm
Maximum torque of stud terminal
10 Nm to 20 Nm
Maximum connectable conductor cross-section
120 mm²
Fuses
None
Quantity
1 (three-phase)
Rated current
3 x 160 A
Rated power
110 kW
Diameter of stud terminal for connecting N and grounding
conductor
10 mm
Diameter of the screws at the fuse switch-disconnector for
connecting L1, L2 and L3
8 mm