beautypg.com

12 technical data of the multicluster box 12.3 – SMA MC-Box 6.3 User Manual

Page 42

background image

12  Technical Data of the Multicluster Box 12.3

SMA Solar Technology AG

42

MC-BOX-6_12-BE-en-20

Operating Manual

12 Technical Data of the Multicluster Box 12.3

General Data

Sunny Island Connection

PV System Connection

Load Connection

Number of line conductors

Three-phase

Nominal voltage (range)

230 V / 400 V
(172,5 V to 250 V / 300 V to 433 V)

Nominal frequency (range)

50 Hz (40 Hz to 70 Hz)

Permitted grid configuration

TN

Mounting type / Installation type

Upright on a base

Quantity

12

Rated current

3 x 104.3 A

Rated power

72 kW

Maximum connectable conductor cross-section

16 mm²

Fuses

12 x circuit breaker C32A

Quantity

1 (three-phase)

Rated current

3 x 160 A

Rated power

110 kW

Diameter of stud terminals

10 mm

Maximum torque of stud terminal

10 Nm to 20 Nm

Maximum connectable conductor cross-section

120 mm²

Fuses

None

Quantity

1 (three-phase)

Rated current

3 x 160 A

Rated power

110 kW

Diameter of stud terminal for connecting N and grounding
conductor

10 mm

Diameter of the screws at the fuse switch-disconnector for
connecting L1, L2 and L3

8 mm

This manual is related to the following products: