11  Technical Data of the Multicluster Box 6.3

SMA Solar Technology AG

40

MC-BOX-6_12-BE-en-20

Operating Manual

Auxiliary Electric Circuits (Fuses F5, F6, F7)

General Data

Fuse

D01

Maximum allowed fuse rating

2 A

Number of line conductors

3

Permitted grid configuration

TN-S

AC voltage range between L1 and N

172.5 V to 250.0 V

AC voltage range between L1 and L2

300 V to 433 V

Rated frequency

50 Hz

Frequency range

40 Hz to 70 Hz

Width x height x depth

760 mm x 760 mm x 210 mm

Weight

55 kg

Maximum installation height above MSL

2,000 m

Inner subdivision*

* in accordance with IEC 61439-1and IEC 61439-2

Form 1, no subdivision

Exterior structure

Closed type

Construction type

Integral parts

Degree of protection of enclosure

IP65

Degree of protection with open enclosure door

IP00

Pollution degree at the mounting location*

3

Pollution degree in the enclosure (microenvironment)*

2

Protection class**

** in accordance with IEC 417

I

Overvoltage category***

*** in accordance with EN 60664

Overvoltage category 3

Rated impulse withstand voltage at 2,000 m above mean sea
level

4 kV

EMC environment*

A

EC declaration of conformity

Yes

Operating temperature range

− 25°C to +50°C

Humidity

0% to 100%