11  Technical Data of the Multicluster Box 6.3

SMA Solar Technology AG

38

MC-BOX-6_12-BE-en-20

Operating Manual

11 Technical Data of the Multicluster Box 6.3

Load Connection

Sunny Island Connection

Generator Connection

Quantity

1 x three-phase

Rated power

55 kW

Rated operating voltage between L and N

230 V

Rated operating voltage between L1 and L2

400 V

Current at rated values

3 x 80 A

Diameter of stud terminal for connecting N

6 mm

Diameter of stud terminal for connecting the grounding conductor 6 mm
Diameter of the screws at the fuse switch-disconnector for
connecting L1, L2, L3

8 mm

Maximum torque of stud terminal

6 Nm

Maximum torque of the fuse switch-disconnector

14 Nm

Maximum connectable conductor cross-section

35 mm²

Fuse

LV/HRC size 00

Maximum allowed fuse rating

80 A

Maximum number of Sunny Island inverters

6

Rated power of the Sunny Island

36 kW

Rated operating voltage between L and N

230 V

Rated operating voltage between L1 and L2

400 V

Current at Sunny Island ratings

3 x 52.2 A

Maximum unaffected short-circuit current at the feed-in terminal

≤ 17 kA

Maximum connectable conductor cross-section

Rigid cable: 25 mm²
Fine-stranded cable: 16 mm²

Fuses

6 x circuit breaker C 40 A

Quantity

1 x three-phase

Rated input power

55 kW

Rated operating voltage between L and N

230 V

Rated operating voltage between L1 and L2

400 V