11  Technical Data of the Multicluster Box 6.3

Operating Manual

MC-BOX-6_12-BE-en-20

39

PV System Connection

Grounding Connection

AC input current

3 x 80 A

Maximum relative short-circuit current at the feed-in terminal

≤ 25 kA

Diameter of stud terminal for connecting N

6 mm

Diameter of stud terminal for connecting the grounding conductor 6 mm
Diameter of the screws at the fuse switch-disconnector for
connecting L1, L2, L3

8 mm

Maximum torque of stud terminal

6 Nm

Maximum torque of the fuse switch-disconnector

14 Nm

Maximum connectable conductor cross-section

35 mm²

Fuse

LV/HRC size 00

Maximum allowed fuse rating

80 A

Quantity

1 x three-phase

Rated power of the PV system

55 kW

Rated operating voltage between L and N

230 V

Rated operating voltage between L1 and L2

400 V

AC current at rated values

3 x 80 A

Maximum relative short-circuit current at the feed-in terminal

≤ 17 kA

Maximum nominal current of the pre-fuse

80 A

Breaking capacity of the pre-fuse in case of short-circuit current

≥ 25 kA

Cut-off current of the fuse

≤ 17 kA

Diameter of stud terminal

6 mm

Maximum torque of stud terminal

6 Nm

Maximum connectable conductor cross-section

35 mm²

Fuse

Not available

Diameter of the screws on the fuse element for connecting the
grounding conductor

6 mm

Maximum torque

6 Nm

Maximum connectable conductor cross-section

35 mm²