10  Technical Data

Operating Manual

BatFuse-BE-en-30

21

10 Technical Data

10.1 Fuse

10.2 Electrical Data

10.3 Battery Terminals

10.4 Sunny Island Charger Terminals

BatFuse-B.01

BatFuse-B.03

Type

LV/HRC size 1

LV/HRC size 1

Approved fuse links

80 A to 250 A

80 A to 250 A

Support

Fuse-switch-disconnector

Fuse-switch-disconnector

Quantity

2

6

Rated voltage

12 V / 24 V / 48 V

Rated current depending on fuse link

80 A / 100 A / 160 A / 200 A / 250 A

Rated voltage of the battery voltage tap

12 V / 24 V / 48 V

Rated current for battery voltage tap

8 A

BatFuse-B.01

BatFuse-B.03

Number of terminals

1

2

Terminal lug

M8

M8

Maximum width of the terminal lug

25 mm

25 mm

Maximum conductor cross-section

95 mm²

95 mm²

External diameter of cables

14 mm to 21 mm

14 mm to 21 mm

BatFuse-B.01

BatFuse-B.03

Number of terminals

2

4

Terminal lug

M8

M8

Maximum width of the terminal lug

16 mm

16 mm

Maximum conductor cross-section

4 x 16 mm²

8 x 16 mm²

External diameter of cables

4 x 9 mm to 16 mm

8 x 9 mm to 16 mm

This manual is related to the following products: