2 connecting the sunny island – SMA BATFUSE-B.01 User Manual
Page 14
6 Electrical Connection
SMA Solar Technology AG
14
BatFuse-BE-en-30
Operating Manual
Terminals Battery Side (C)
6.2 Connecting the Sunny Island
Figure 5: Overview of terminals
Cable requirements:
☐ Conductor cross-section: specified by the Sunny Island
☐ External diameter: 14 mm to 21 mm
☐ Material of the conductor: copper
☐ Terminal lugs size M8, maximum width: 25 mm
Procedure:
1. Loosen the four screws of the enclosure lid.
2. Remove the enclosure lid of the BatFuse.
3. Open the load-break switch and remove it from the support.
4. Remove the cover.
5. Mount the terminal lugs on the DC+ cable and on the DC − cable of the Sunny Island.
BatFuse-B.01
BatFuse-B.03
Number of components to be
connected
One battery and a maximum of
two Sunny Island Charger
devices
One battery and a maximum of
four Sunny Island Charger
devices
External diameter of cables for
the battery
1 x 14 mm to 21 mm
2 x 14 mm to 21 mm
External diameter of cables for
the Sunny Island Charger
9 mm to 16 mm
9 mm to 16 mm
Terminal lug
M8, maximum width: 25 mm
M8, maximum width: 25 mm
Position
Designation
A
Terminal L+
B
Terminal L −