7 Commissioning
SMA Solar Technology AG
26
FSS-IS-en-40
Installation Manual - Quick Reference Guide
7.2.3 Adjusting the Configuration for France
Requirement:
☐ The extended configuration must be performed within the first ten operating hours of the Sunny Island, otherwise an
SMA Grid Guard code is required in order to change grid-relevant parameters (application form for the SMA Grid
Guard code available at www.SMA-Solar.com).
☐ The country data set of the Sunny Island must be set to VDE-AR-4105 (see Section 7.1 "Basic Configuration of the
Sunny Island Inverter", page 21).
Procedure:
1. Switch to expert mode on the Sunny Remote Control (see Sunny Island inverter operating manual).
2. Set the parameter 232.07 GdFrqMax to 50.6 Hz.
3. Set the parameter 232.15 GdFrqMaxDel to 0.05 Hz.
4. Set the parameter 232.08 GdVldTm to 30 s.
7.2.4 Adjusting the Configuration for Austria
If your grid operator does not permit frequency-dependent control of active power feed-in in the case of overfrequency,
you must switch off this function (see VDE-AR-N 4105 item 5.7.3.3). If your grid operator specifies a maximum grid
feed-in per line conductor, you must reduce the discharge/charging current (default setting in the Sunny Island is max.
20.0 A).
Requirement:
☐ The extended configuration must be performed within the first ten operating hours of the Sunny Island, otherwise an
SMA Grid Guard code is required in order to change grid-relevant parameters (application form for the SMA Grid
Guard code available at www.SMA-Solar.com).
☐ The country data set of the Sunny Island must be set to VDE-AR-4105 (see Section 7.1 "Basic Configuration of the
Sunny Island Inverter", page 21).
Procedure:
1. Switch to expert mode on the Sunny Remote Control (see Sunny Island inverter operating manual).
2. If frequency-dependent control of active power feed-in is not permitted, set the parameter 232.41 P-WCtLHzMod
to Off.
3. If your grid operator specifies a maximum grid feed-in per line conductor, set the parameter
210.03 InvChrgCurMax to the value specified by the grid operator.
7.2.5 Adjusting the Configuration for Switzerland
The following limiting values must be adjusted in order to meet the requirements of the grid operators in Switzerland:
• Maximum power frequency
• The upper frequency difference for valid grid connection
• Minimum observation time for grid voltage and frequency in the permissible range for grid connection
If your grid operator specifies a maximum grid feed-in per line conductor, you also must reduce the discharge/charging
current (default setting in the Sunny Island is max. 20.0 A).
Requirement:
☐ The extended configuration must be performed within the first ten operating hours of the Sunny Island, otherwise an
SMA Grid Guard code is required in order to change grid-relevant parameters (application form for the
SMA Grid Guard code available at www.SMA-Solar.com).
☐ The country data set of the Sunny Island must be set to VDE-AR-4105 (see Section 7.1 "Basic Configuration of the