7  Commissioning

SMA Solar Technology AG

26

FSS-IS-en-40

Installation Manual - Quick Reference Guide

7.2.3 Adjusting the Configuration for France

Requirement:

☐ The extended configuration must be performed within the first ten operating hours of the Sunny Island, otherwise an

SMA Grid Guard code is required in order to change grid-relevant parameters (application form for the SMA Grid

Guard code available at www.SMA-Solar.com).

☐ The country data set of the Sunny Island must be set to VDE-AR-4105 (see Section 7.1 "Basic Configuration of the

Sunny Island Inverter", page 21).

Procedure:

1. Switch to expert mode on the Sunny Remote Control (see Sunny Island inverter operating manual).
2. Set the parameter 232.07 GdFrqMax to 50.6 Hz.
3. Set the parameter 232.15 GdFrqMaxDel to 0.05 Hz.
4. Set the parameter 232.08 GdVldTm to 30 s.

7.2.4 Adjusting the Configuration for Austria

If your grid operator does not permit frequency-dependent control of active power feed-in in the case of overfrequency,

you must switch off this function (see VDE-AR-N 4105 item 5.7.3.3). If your grid operator specifies a maximum grid

feed-in per line conductor, you must reduce the discharge/charging current (default setting in the Sunny Island is max.

20.0 A).

Requirement:

☐ The extended configuration must be performed within the first ten operating hours of the Sunny Island, otherwise an

SMA Grid Guard code is required in order to change grid-relevant parameters (application form for the SMA Grid

Guard code available at www.SMA-Solar.com).

☐ The country data set of the Sunny Island must be set to VDE-AR-4105 (see Section 7.1 "Basic Configuration of the

Sunny Island Inverter", page 21).

Procedure:

1. Switch to expert mode on the Sunny Remote Control (see Sunny Island inverter operating manual).
2. If frequency-dependent control of active power feed-in is not permitted, set the parameter 232.41 P-WCtLHzMod

to Off.

3. If your grid operator specifies a maximum grid feed-in per line conductor, set the parameter

210.03 InvChrgCurMax to the value specified by the grid operator.

7.2.5 Adjusting the Configuration for Switzerland

The following limiting values must be adjusted in order to meet the requirements of the grid operators in Switzerland:

• Maximum power frequency
• The upper frequency difference for valid grid connection
• Minimum observation time for grid voltage and frequency in the permissible range for grid connection

If your grid operator specifies a maximum grid feed-in per line conductor, you also must reduce the discharge/charging

current (default setting in the Sunny Island is max. 20.0 A).

Requirement:

☐ The extended configuration must be performed within the first ten operating hours of the Sunny Island, otherwise an

SMA Grid Guard code is required in order to change grid-relevant parameters (application form for the

SMA Grid Guard code available at www.SMA-Solar.com).

☐ The country data set of the Sunny Island must be set to VDE-AR-4105 (see Section 7.1 "Basic Configuration of the

Sunny Island Inverter", page 21).