2 connecting the sunny island – SMA SI 3.0-11 Quick Reference Guide V.4.0 User Manual

Page 14

background image

4  System With One Sunny Island

SMA Solar Technology AG

14

FSS-IS-en-40

Installation Manual - Quick Reference Guide

4.2 Connecting the Sunny Island

Figure 2: Connecting the Sunny Island inverter

Position

Designation

Description/information

A

AC power cable

Connection AC2 Gen/Grid terminals L, N

TT

,

and PE

Utility grid connection with a three-wire cable
Conductor cross-section: 6 mm² to 16 mm²

B

Grounding conductor

Terminal AC1 Loads/SunnyBoys terminal PE
Additional grounding if the conductor cross-section of the AC power

cable is less than 10 mm².
The conductor cross-section must equal at least the conductor

cross-section of the AC power cable.

C

DC+ cable

Battery connection
Conductor cross-section: 50 mm² to 95 mm²
Cable diameter: 14 mm to 25 mm

D

DC − cable

E

Measuring cable of the battery

temperature sensor

Terminal BatTmp
You only have to connect a battery temperature sensor if lead-acid

batteries are used.
Mount the battery temperature sensor in the middle of the battery

connection, in the upper third of the battery cell.