3  Information and System Description

SMA Solar Technology AG

10

FSS-IS-en-40

Installation Manual - Quick Reference Guide

3 Information and System Description

3.1 Requirements of the "VDE Forum Network Technology / Network

Operations (FNN)"

The information below only applies for systems for which the following properties are all applicable:

• Only one Sunny Island is connected in the system.
• The grid operator requires compliance with the Technical Information "Connection and Operation of Storage Units"

of the FNN. Currently, only the grid operators in Germany require compliance with the above-mentioned Technical

Information (status: June 2014).

In these systems, the Sunny Island must be connected to a line conductor supplied by a single-phase PV inverter. If there

are only three-phase PV inverters connected in the system, the Sunny Island can be connected to any line conductor.
The requirements of the Technical Information "Connection and Operation of Storage Units in Low-Voltage Networks"

published by the FNN influence the discharge behavior of the Sunny Island inverter. In systems with one Sunny Island

and single-phase PV inverters, the SMA Flexible Storage System reduces the maximum discharge power of the

Sunny Island as required.
Example 1:
All PV inverters are single-phase and are feeding in asymmetrically

(Sunny Boy). The PV inverters are connected to one line conductor.

The Sunny Island must be connected to the line conductor into which

the PV inverters are feeding.

Example 2:
All PV inverters are single-phase and are feeding in asymmetrically

(Sunny Boy). PV inverters are connected to two line conductors.

The Sunny Island must be connected to a line conductor into which

a single-phase PV inverter is feeding. TIP: Connect the Sunny Island

to the line conductor being supplied with the least PV energy. This

will increase the control range for increased self-consumption.

Example 3:
All PV inverters are single-phase and are feeding in asymmetrically

(Sunny Boy). One PV inverter is connected to each line conductor.

The Sunny Island can be connected to any line conductor.

TIP: Connect the Sunny Island to the line conductor being supplied

with the least PV energy. This will increase the control range for

increased self-consumption.