2 connecting the master – SMA SI 3.0-11 Quick Reference Guide V.4.0 User Manual
Page 17
SMA Solar Technology AG
5 System With Three Sunny Island Inverters
Installation Manual - Quick Reference Guide
FSS-IS-en-40
17
5.2 Connecting the Master
Figure 4: Connecting the master
Position
Designation
Description/information
A
AC power cable
Terminals AC2 Gen/Grid terminals L, N
TT
,
and PE
Utility grid connection with a three-wire cable to the line conductor L1
Conductor cross-section: 6 mm² to 16 mm²
B
Grounding conductor
Terminal AC1 Loads/SunnyBoys terminal PE
Additional grounding if the conductor cross-section of the AC power
cable is less than 10 mm²
The conductor cross-section must equal at least the conductor
cross-section of the AC power cable.
C
DC+ cable
Battery connection
Conductor cross-section: 50 mm² to 95 mm²
Cable diameter: 14 mm to 25 mm
D
DC − cable
E
Measuring cable of the battery
temperature sensor
Terminal BatTmp
You only have to connect a battery temperature sensor if lead-acid
batteries are used.
Mount the battery temperature sensor in the middle of the battery
connection, in the upper third of the battery cell.