2 adjusting the configuration for denmark – SMA SI 3.0-11 Quick Reference Guide V.4.0 User Manual
Page 25

SMA Solar Technology AG
7 Commissioning
Installation Manual - Quick Reference Guide
FSS-IS-en-40
25
7.2 Adjusting the Configuration of the Sunny Island Inverter
7.2.1 Countries in Which the Configuration Must Be Adjusted
In the SMA Flexible Storage System, the Sunny Island inverters are connected to the utility grid and must meet the
requirements of the grid operators. Depending on the settings, the Sunny Island inverters satisfy the requirements of the
application rule VDE-AR-N 4105:2011-08 or the standard AS4777. The application rule is stored in the Sunny Island
inverters as the standard country data set VDE-AR-4105 or AS4777. The configuration must be adjusted for the
following countries (status: July 2014):
• Denmark (see Section 7.2.2, page 25)
• France (see Section 7.2.3, page 26)
• Austria (see Section 7.2.4, page 26)
• Switzerland (see Section 7.2.5, page 26)
The configuration may only be adjusted on request or with permission of the grid operator in the following countries
(status: July 2014):
• Australia
Country data set: AS4777
• Belgium
Country data set: VDE-AR-4105
• Germany
Country data set: VDE-AR-4105
Use in other countries is possible with the agreement of the grid operator. Consult the grid operator on whether
adjustment is necessary.
7.2.2 Adjusting the Configuration for Denmark
When using the Sunny Island 6.0H / 8.0H in Denmark, you must reduce the discharge/charging current (default setting:
max. 20.0 A).
When using the Sunny Island 3.0M / 4.4M in Denmark, you can retain the default setting of the discharge/charging
current (default setting: max. 16.0 A).
Requirement:
☐ The extended configuration must be performed within the first ten operating hours of the Sunny Island, otherwise an
SMA Grid Guard code is required in order to change grid-relevant parameters (application form for the SMA Grid
Guard code available at www.SMA-Solar.com).
☐ The country data set of the Sunny Island must be set to VDE-AR-4105 (see Section 7.1 "Basic Configuration of the
Sunny Island Inverter", page 21).
Procedure:
1. Switch to expert mode on the Sunny Remote Control (see the Sunny Island inverter operating manual).
2. Set the parameter 210.03 InvChrgCurMax to 16.0 A.