9  Maintenance when Control Voltage is Present

SMA America, LLC

48

SCCP-US-WH-US_en-30

Maintenance Manual

9.3 Checking the Heating Element, Hygrostat and Fan

Figure 13: Positions of the heating element, hygrostat and fans (left image standard unit, right image with Integrated DC Switch)

Requirement:

☐ There are no disturbances.

'$1*(5

Danger to life due to electric shock when opening the inverter cabinet
There are live components behind the doors of the inverter cabinet.

• Wear Hazard Risk Category 2 personal protective equipment.
• Always perform work in compliance with the regulations specified in 29 CFR, Chapter XVII, Part 1910 (OSHA),

NEC, and NFPA 70E.

&$87,21

Risk of burns due to hot parts of the heating element
During the functional test, the heating element becomes hot. There is a risk of burns if you touch the heating element

without protective gloves.

• Do not touch heating elements with bare hands.
• Wear personal protective equipment.
• Always maintain a suitable distance when checking the function of the heating elements.

Low humidity
If humidity is below 50%, you will not be able to perform the function test since the minimum value of the hygrostat

is 50%.

Position

Designation

A

Heater

B

Fans

C

Hygrostat