3  Product Description

Maintenance Manual

SCCP-US-WH-US_en-30

17

Inverter with External AC Disconnect and External DC Disconnect

As an option, the internal AC circuit breaker of the inverter can be mounted externally.

Figure 3: Principle of a grid-tie PV plant with an inverter without integrated AC Disconnect

Position

Designation

A

PV modules

B

String-Combiner

C

Inverter with integrated AC Disconnect

D

DC Disconnect Unit

E

External transformer

F

Utility grid

Circuit breaker
The unit is provided with a UL listed circuit breaker on the output rated 1,600 A for branch circuit protection. If the

circuit breaker shall be located externally to secure the AC path, you have to use the same type of circuit breaker

(ABB Emax E2B-A with 42 kA rated short-circuit current, ABB Emax E2N-A with 65 kA rated short-circuit current or

ABB Emax E2H-A with 85 kA rated short-circuit current and and 1,600 A continuous current rating each).

Position

Designation

A

PV modules

B

String-Combiner

C

Inverter without integrated AC Disconnect and without integrated DC switch

D

AC / DC Disconnect Unit

E

External transformer

F

Utility grid