SMA SC 500CP-US Maintenance Manual User Manual
Page 17
SMA America, LLC
3 Product Description
Maintenance Manual
SCCP-US-WH-US_en-30
17
Inverter with External AC Disconnect and External DC Disconnect
As an option, the internal AC circuit breaker of the inverter can be mounted externally.
Figure 3: Principle of a grid-tie PV plant with an inverter without integrated AC Disconnect
Position
Designation
A
PV modules
B
String-Combiner
C
Inverter with integrated AC Disconnect
D
DC Disconnect Unit
E
External transformer
F
Utility grid
Circuit breaker
The unit is provided with a UL listed circuit breaker on the output rated 1,600 A for branch circuit protection. If the
circuit breaker shall be located externally to secure the AC path, you have to use the same type of circuit breaker
(ABB Emax E2B-A with 42 kA rated short-circuit current, ABB Emax E2N-A with 65 kA rated short-circuit current or
ABB Emax E2H-A with 85 kA rated short-circuit current and and 1,600 A continuous current rating each).
Position
Designation
A
PV modules
B
String-Combiner
C
Inverter without integrated AC Disconnect and without integrated DC switch
D
AC / DC Disconnect Unit
E
External transformer
F
Utility grid