7  Maintenance in Disconnected State

SMA America, LLC

28

SCCP-US-WH-US_en-30

Maintenance Manual

14. Disconnect the circuit breaker of the 24 V circuits.

15. Open the test and disconnect terminals.

16. Ensure that all poles are free of voltage.
17. Ground and short-circuit the inverter.
18. Cover or shield any adjacent live components.
19. Unscrew the protective cover over the fuses.
20. Remove all DC fuses from all DC fuse holders. Use a suitable tool or safety gloves.

7 Maintenance in Disconnected State

7.1 Safety

'$1*(5

Danger to life due to electric shock
High voltages that can result in lethal electrical shocks are present in the live components of the inverter.

• All work must be carried out in accordance with this document.
• Do not touch any live components in the inverter or on the medium-voltage grid. Comply with all applicable safety

regulations for handling medium-voltage grids.

• After disconnection, wait at least 15 minutes until the capacitors have discharged.
• Follow all safety precautions (see Section 2.2).
• Disconnect the inverter (see Section 6).