beautypg.com

SMA SC 500CP-US Maintenance Manual User Manual

Page 35

background image

SMA America, LLC

7  Maintenance in Disconnected State

Maintenance Manual

SCCP-US-WH-US_en-30

35

– Insert the new surge arrester into the top-hat rail from above and

press it against the top-hat rail.

– Connect the cables to the same terminals of the surge arrester from which they were previously removed.

5. Close the interface cabinet.

7.8 Checking the Screw Connection of the Power Cabling

Figure 8: Position of the power cabling

/05*$&

Damage to screw connections from over-tightening

• Only tighten loose connections applying the prescribed torque. Torque specifications are shown in the installation

manual of the inverter. Contact the SMA Service Line if specifications are missing.

Position

Designation

A

For negative grounding: connection busbar of the DC − cables
For positive grounding: connection busbar of the DC+ cables

B

For negative grounding: connection busbar of the DC − cables
For negative grounding: connection lugs of the DC+ cables

C

Connection lugs of the AC cables

D

Connection busbar of the grounding cables