beautypg.com

3 personal protective equipment, 4 symbols on the inverter – SMA SC 500CP-US Maintenance Manual User Manual

Page 15

background image

SMA America, LLC

2  Safety

Maintenance Manual

SCCP-US-WH-US_en-30

15

2.3 Personal Protective Equipment

Always wear the personal protective equipment recommended by SMA America, LLC when working on the inverter. All

clothing should be in accordance with NFPA 70E Section 130.7. Appropriate Insulated gloves for shock protection in

accordance with NFPA 70E Section 130.7(C), rated at least 1000V shall be worn as required.
Any other prescribed protective equipment must also be used. When carrying out work on live parts of the inverter,

protective equipment of at least Hazard Risk Category 2 is required in accordance with NEMA NFPA 70E, Table

130.7(C)(16).

2.4 Symbols on the inverter

Hazard Risk Category 2 protective equipment required
In accordance to NFPA 70E, an arc flash hazard risk analysis has been performed by SMA, and appropriate Arc

Flash Hazard labels stating the required Personal Protective Equipment (PPE) for exposed, energized interaction with

the equipment, are installed. Hazard Risk Category 2 PPE is the requirement for all routine maintenance, diagnostics,

and commissioning activities as described in the SMA protocols. Areas within the machine also exist that cannot,

under any circumstances, be exposed while energized.
For additional information, please contact the SMA Service Line.

Symbol

Explanation
DC current

Earth Ground

AC current

On position of the AC Disconnect

Off position of the AC Disconnect