beautypg.com

11 technical data – SMA 600-US User Manual

Page 48

background image

11  Technical Data

SMA America, LLC

48

CU600-1000US-IA-en-10

Installation Manual

11 Technical Data

DC Input

DC Output

Protective Devices

Torques

CU 600-US-10

CU 1000-US-10

Maximum number of incoming strings

8

8

Strings for INPUT A

4

4

Strings for INPUT B

4

4

Maximum input voltage

600 V

1,000 V

CU 600-US-10

CU 1000-US-10

Maximum number of outgoing strings

2

2

CU 600-US-10

CU 1000-US-10

DC reverse polarity detection

Not available

available

Overcurrent protection

String fuses

String fuses

CU 600-US-10

CU 1000-US-10

Fuse holder / terminals for connecting the DC
input cables

30 in-lb. (3.4 Nm)

15 in-lb. (1.7 Nm)

Terminals for connecting the DC output cables

51 in-lb. (5.8 Nm)

51 in-lb. (5.8 Nm)

Grounding terminals

51 in-lb. (5.8 Nm)

51 in-lb. (5.8 Nm)

Lid screws

35.4 in-lb. (4.0 Nm)

35.4 in-lb. (4.0 Nm)

This manual is related to the following products: