6  Electrical Connection

SMA America, LLC

32

CU600-1000US-IA-en-10

Installation Manual

Requirements:

☐ All conduits must be correctly connected to the Connection Unit (see Section 6.3).
☐ The DC switch-disconnector must be turned OFF and the lid of the Connection Unit must be

dismantled.

Procedure:

2. Lead the grounding conductors trough the conduit into the interior of the Connection Unit.
3. Strip the insulation of the grounding conductor

23

32

in. (18 mm).

4. Connect the grounding conductor to one of the

termination points of the terminal with the symbol

and tighten with a screwdriver (blade width: 6

mm) (torque: at least 44.3 in-lb. (5 Nm)).

5. Ensure that the grounding conductor is firmly positioned.

1.

Danger to life due to electric shock

• Make sure all devices connected to the Connection Unit (e.g inverter) are switched off

and protected against reconnection (see manual of the respective device).

• Ensure that no DC voltage is present.