beautypg.com

Connection unit – SMA 600-US User Manual

Page 38

background image

6  Electrical Connection

SMA America, LLC

38

CU600-1000US-IA-en-10

Installation Manual

6.8 Connecting the DC Output Cable for the Inverter to the

Connection Unit

Additionally required mounting material (not included in the scope of delivery):

☐ Two cables for connecting the Connection Unit to the inverter.
☐ If the DC switch-disconnector should be protected against restarting, a padlock can be used.

Cable requirements:

☐ The DC output cables must be designed in accordance with the installation requirements

applicable on site and for temperatures of +194°F (+90°C).

☐ Cable type: copper wire
☐ Use only solid wire or rough wire strands.
☐ Conductor cross-section: AWG 8 to AWG 2 (10 mm² to 35 mm²)

Padlock requirements:

☐ The material must be non-corrosive and weather-proof.
☐ The shackle of the padlock must be hardened.
☐ The lock cylinder must be secured.

Requirements:

☐ The conduits must be correctly connected to the Connection Unit (see Section 6.3).
☐ The DC switch-disconnector must be switched OFF and the lid must be dismantled.

Procedure:
Connect the DC output cables for connecting the Connection Unit to the inverter for INPUT A and
INPUT B as follows:

2. Strip the insulation of the cable ends of the two cables for connecting the Connection Unit to the

inverter by

5

16

in. (18 mm).

3. Connect a cable to the screw terminal with the

minus sign for connecting the Connection Unit to the
inverter.

4. Tighten the screw terminals with a screwdriver

(blade width: 6 mm) (torque 51 in-lb. (5.8 Nm)).

1.

Danger to life due to electric shock

• Make sure all devices connected to the Connection Unit (e.g inverter) are switched off

and protected against reconnection (see manual of the respective device).

• Cover the PV modules.

This manual is related to the following products: