6  Electrical Connection

Installation Manual

CU600-1000US-IA-en-10

35

6.6 Connecting the PV Array to the Connection Unit 1000-US

Cable requirements:

☐ The DC cables of the PV array must be designed in accordance with the installation

requirements applicable on site and for temperatures of +194°F (+90°C).

☐ The DC input and output circuits are isolated from the enclosure and that system grounding, if

required by Section 250 of the National Electrical Code

®

, ANSI/NFPA 70, is the responsibility

of the installer.

☐ The maximum cable length, which is dependent on the conductor cross-section, must be

adhered to.

☐ Cable type: copper wire
☐ Conductor cross-section: AWG 12 to AWG 6 (4 mm² to 16 mm²)

Requirements:

☐ The conduits must be correctly connected to the Connection Unit (see Section 6.3).
☐ The DC switch-disconnector must be switched OFF and the lid must be dismantled.

Procedure:
Connect the DC cables of the PV array to INPUT A and B as follows:

3. Lead the DC cables of the PV array through the connected conduits into the interior of the

Connection Unit.

1.

Danger to life due to electric shock

• Make sure that all devices (e.g. inverter) connected to the Connection Unit are switched

off and protected against reconnection (see manual of the respective device).

• Cover the PV modules.

2.

Danger to life due to electric shock
The strings in the Connection Unit are combined to one main string. If there is reverse polarity
of a PV string, there can be short-circuit current flowing when string fuses are inserted, string
safety levers are closed, and the DC switch-disconnector is open.

• Open all safety levers all the way.