5.5.4

Connections

Cable feed-throughs

Figure 5-4

Cable feed-throughs on the underside of the housing (2 x M32, 24 x M16)

Screw connection:

For wiring use a screwdriver with the correct blade width.

For a reliable and touch-proof connection, use a suitable cable cross section and insu-

late the cable ends according to the above-mentioned specifications.

Spring-cage connection:

WARNING: Dangerous contact voltage

Disconnect the power supply before starting work.

Table 5-1

Assignment of the cable feed-throughs

Number

Connection/cable feed-through

1

Solar strings input (+)

2

DC 1000 V output (+)

3

DC 1000 V output (-)

4

Solar strings input (-)

Table 5-2

Connection terminal blocks

Terminal block

Solid

conductor

[mm²]

Stranded

conductor

[mm²]

Stripping

length [mm]

Torque

[Nm]

UK 10,3-HESI 1000V

1.5 ... 25

0.75 ... 25

11

2 ... 2.5

UKH 150/BU

35 ... 150

50 ... 150

40

25 ... 30

Terminal block

Solid

conductor

[mm²]

Stranded

conductor

[mm²]

Stripping

length [mm]

STU 35/ 4X10 BU

0.2 ... 10

0.2 ... 6

12

M32

M16

M16

1

4

2

3