Dc input, Dc output – SMA CBL-DC-CMB1-10 User Manual
Page 12
CBL-DC-CMB1-10
12
PHOENIX CONTACT
106183_en_00
Type of cable entry
Cable glands
Torques
See “Torques for conductive connections” on page 16
Information on the installation location
See installation site information in section
“General safety notes” on page 7
Ambient temperature (operation)
-25°C … 60°C (derating above +45°C)
Ambient temperature (storage/transport)
-40°C … 60°C
Humidity (operation/storage/transport)
5 ... 95 %, non-condensing
Altitude
≤ 2000 m (amsl (above mean sea level))
DC input
Number of strings
12
Fuse holder
12 x UK 10,3-HESI 1000 V
Fuse type
10.3 x 38 fuses for DC 1000 V
Fuse size
2 A … 20 A
Terminals for + side
3 x STU 35/ 4X10
Terminals for - side
3 x STU 35/ 4X10 BU
Cable glands
24 x M16
Clamping area
5 ... 10 mm
Conductor cross section
4 … 6 mm²
Terminal type for + side
Screw connection with M5 screws
(see “Torques for conductive connections” on page 16)
Terminal type for - side
Spring connection
DC output
Cable glands
2 x M32
Clamping area
18 ... 25 mm
Conductor cross section solid
35 … 95 mm²
Conductor cross section solid AWG
2 - 4/0
Conductor cross section stranded
50 … 95 mm²
Conductor cross section stranded AWG
1/0 - 4/0
Conductor material
Copper or aluminum
When connecting aluminum conductors, please refer to the “Notes and prod-
uct release list for connecting aluminum conductors” document. This can be
found at phoenixcontact.com in the download area for article 3010110.
Terminal type
Screw connection with M10 screws
(see “Torques for conductive connections” on page 16)
Terminal output for + side
1 x UKH 150
Terminal output for - side
1 x UKH 150 BU
Technical data