beautypg.com

Dc input, Dc output – SMA CBL-DC-CMB1-10 User Manual

Page 12

background image

CBL-DC-CMB1-10

12

PHOENIX CONTACT

106183_en_00

Type of cable entry

Cable glands

Torques

See “Torques for conductive connections” on page 16

Information on the installation location

See installation site information in section

“General safety notes” on page 7

Ambient temperature (operation)

-25°C … 60°C (derating above +45°C)

Ambient temperature (storage/transport)

-40°C … 60°C

Humidity (operation/storage/transport)

5 ... 95 %, non-condensing

Altitude

≤ 2000 m (amsl (above mean sea level))

DC input

Number of strings

12

Fuse holder

12 x UK 10,3-HESI 1000 V

Fuse type

10.3 x 38 fuses for DC 1000 V

Fuse size

2 A … 20 A

Terminals for + side

3 x STU 35/ 4X10

Terminals for - side

3 x STU 35/ 4X10 BU

Cable glands

24 x M16

Clamping area

5 ... 10 mm

Conductor cross section

4 … 6 mm²

Terminal type for + side

Screw connection with M5 screws

(see “Torques for conductive connections” on page 16)

Terminal type for - side

Spring connection

DC output

Cable glands

2 x M32

Clamping area

18 ... 25 mm

Conductor cross section solid

35 … 95 mm²

Conductor cross section solid AWG

2 - 4/0

Conductor cross section stranded

50 … 95 mm²

Conductor cross section stranded AWG

1/0 - 4/0

Conductor material

Copper or aluminum

When connecting aluminum conductors, please refer to the “Notes and prod-

uct release list for connecting aluminum conductors” document. This can be

found at phoenixcontact.com in the download area for article 3010110.

Terminal type

Screw connection with M10 screws

(see “Torques for conductive connections” on page 16)

Terminal output for + side

1 x UKH 150

Terminal output for - side

1 x UKH 150 BU

Technical data