3 derating diagram, Derating diagram – SMA CBL-DC-CMB1-10 User Manual
Page 13

CBL-DC-CMB1-10
106183_en_00
PHOENIX CONTACT
13
5.3
Derating diagram
The current per string must be decreased as shown in the derating diagram below, depend-
ing on ambient temperatures higher than +45°C. For each +1°C temperature increase, the
current per string must be decreased with 0,24A. The calculated derating is 1,5 % per +1°C,
in relation to the nominal current.
Ambient temperature in °C
Figure 5-1
Current per string
Current per string
16,0
14,8
13,6
12,4
8,0
9,0
10,0
11,0
12,0
13,0
14,0
15,0
16,0
17,0
18,0
45
50
55
60
Cu
rr
en
t p
e
r s
tr
in
g
i
n
A
This manual is related to the following products: